Direct acting regulator
It consists of measuring element (film), transmission part (valve) and adjustment mechanism (valve) (Fig. 1). When the amount of gas used after the outlet increases or the inlet pressure decreases, the outlet pressure drops, and the pressure reflected by the pressure guiding tube acts.
The force on the underside of the film is less than the force of the weight (or spring) on the film, the film is lowered, and the valve flap moves down with the valve stem, causing the valve to open, the gas flow rate to increase, and the outlet pressure to return to the original given value. Conversely, when the amount of gas used after the outlet is reduced or the inlet pressure is increased, the valve is closed and the flow rate is reduced, and the outlet pressure is still restored. The outlet pressure value can be given by adjusting the weight or spring force of the weight. Small liquefied petroleum gas pressure reducing valves and user pressure regulators are all direct acting.
Indirect acting regulator
It consists of a main regulator, pilot and exhaust valve. When the outlet pressure p2 is lower than a given value, the film of the pilot is lowered, the pilot valve is opened, and the gas of pressure p3 is replenished to the membrane space of the main regulator after throttling. Since p3 is greater than p2, the main regulator valve is opened, the flow rate is increased, and p2 is restored to a given value. Conversely, when p2 exceeds a given value, the pilot film rises and the valve closes. At the same time, due to the force acting on the lower side of the exhaust valve film, the exhaust valve is opened, and a part of the gas with a pressure of p3 is discharged into the atmosphere, so that the force on the lower side of the main regulator film is reduced, and since p2 is too large, The valve of the main regulator is closed, and p2 is restored to the given value. Gas storage and distribution stations, regional pressure regulating stations and large-scale user-specific pressure regulating stations basically use indirect acting regulators.
The gas pressure of the safe use of liquefied petroleum gas water heaters and gas stoves in China is 2800Pa, and the gas pressure in bottled liquefied petroleum gas cylinders is generally 4kg. After the pressure of the cylinder is reduced to 0.028kg (ie 2800Pa) For use in water heaters or gas stoves.
Axial flow regulator:
The axial flow regulator is a command type pressure regulator with novel structure, tight sealing, large circulation capacity and stable pressure regulation. The internal parts of the pressure regulator are made of stainless steel, with long service life, with automatic over-pressure shut-off and pressure recovery. Automatic opening function in normal time, small installation space, can be installed in any position, suitable for urban gate station, regional pressure regulating station and gas turbine gas supply, can be used for natural gas, liquefied petroleum gas, air and other non-corrosive gases.
Working principle: The pressure regulator consists of five parts: the intake valve body, the air inlet body, the air outlet body, the air outlet valve body and the pilot. The air inlet body is equipped with a main valve pressure regulating spring, a high pressure gas cylinder sleeve and a sealing film. Wait. The outlet valve body is provided with a fixed valve seat, and the valve seat and the high pressure gas cylinder sleeve constitute a sealing pair. When the pilot is closed, the high pressure gas cylinder is placed under the action of the main valve spring, and is closely attached to the fixed valve seat to close the medium in the pressure regulator; when the pilot is opened, the pilot is guided by the gas The film pulls the sealing film pressure plate to press the spring, so that the high pressure gas cylinder cover leaves the fixed valve seat, and the larger the command valve is opened, the larger the gap between the high pressure gas cylinder sleeve and the fixed valve seat, thereby realizing the function of adjusting the air flow pressure and the flow rate.